Daylight harvesting dims electric lights when useful daylight reaches a space. A good system saves electricity while keeping the work area comfortable and adequately lit. Its success depends less on the sensor alone than on zoning, placement, calibration and commissioning.
How daylight harvesting works
A photosensor reports a light level to a controller. The controller compares that signal with its target and tells compatible LED drivers to dim, hold or raise the output of the luminaires in that control zone. Occupancy sensing and schedules may also affect the command. The sensor’s reading is not automatically the illuminance on a desk: its field of view, mounting position and the room’s reflectance all matter.
In a DALI-2 system, light sensors are specified under Part 304 and occupancy sensors under Part 303. Some products combine both functions. An input device provides information; an application controller decides what to do with it, so check the full system’s compatibility rather than the sensor label alone. The DALI Alliance’s sensor guide explains these roles and the light sensor’s programmable hysteresis.
Open-loop or closed-loop control?
| Approach | What the sensor sees | Design implication |
|---|---|---|
| Open loop | Representative daylight, without the controlled electric light | Place and orient it so the signal reflects daylight available to its zone. |
| Closed loop | Daylight plus light from the luminaires and room surfaces | Calibrate carefully: changes to furniture or reflectance can change the feedback. |
Neither approach is universally best. The U.S. federal LED and controls guidance describes both and recommends selecting the arrangement for the application. Test the actual response in the installed room.
Divide the room into sensible daylight zones
Luminaires beside a window may need to dim while those deeper in the room remain near full output. Do not place an entire floor on one daylight signal merely because its lights share a circuit. Group luminaires by their access to daylight, considering facade orientation, window height, glazing, blinds, external obstructions and the work positions. Separate facades where sunlight behaves differently.
Start with a plan of the windows and the luminaire rows. For each proposed zone, ask whether its darkest occupied task position will still have enough light when the window-side luminaires dim. Code-defined daylight zone boundaries vary by jurisdiction and project; use the rules applicable to the actual building for compliance.
Where should the photosensor go?
- Keep direct sun, unusually bright surfaces and the controlled luminaire out of the sensor’s view unless the chosen control method explicitly requires them.
- Check that partitions, signs, shelves and furniture will not block the view after fit-out.
- Use more than one sensor or zone when one reading cannot represent the different conditions in the room.
- Measure illuminance at the task plane during calibration; do not assume a ceiling sensor reports the same lux value.
The Whole Building Design Guide’s photosensor technical note highlights calibration and commissioning. A poorly tuned system may deliver little energy benefit and frustrate occupants.
Setpoint, deadband, fade time and minimum level
The setpoint is the target used by the control algorithm. A deadband or hysteresis prevents small daylight fluctuations from repeatedly moving the lights. Fade time determines how quickly changes appear. The minimum level sets how low a luminaire may dim before it holds or turns off. Verify the chosen driver and luminaire remain stable at that level. Record all four settings at handover so a technician can reproduce the intended behaviour.
Illustrative example: imagine a desk receives 450 lux from electric lighting at full output and 300 lux from daylight on one afternoon. Those readings do not justify commanding the electric system to “200 lux” by simple subtraction. A ceiling sensor may see a different mix of light. Measure several task points, relate them to the sensor signal, then tune the output so the least-lit occupied position still meets the project’s target.
Commissioning checklist
- Confirm which sensor controls each luminaire group and verify manual override.
- Measure the work plane in different daylight and blind conditions, including a condition with little daylight.
- Watch for hunting, abrupt changes and dark areas while people move through the space.
- Test occupancy sensing, schedules, power restoration and the minimum dimming level together.
- Save the zone map, addresses, controller settings and configuration backup; revisit the settings after furniture and blinds are in normal use.
There is no reliable universal savings percentage. Orientation, glazing, climate, operating hours, lighting power, dimming range and blind use all affect the result. Estimate energy by zone and schedule, then compare with metered or control-system data after occupancy.
Frequently asked questions
Can one photosensor control a whole office?
Only if its reading represents the daylight conditions and lighting needs of every controlled area. Window and interior rows usually need separate groups.
Does daylight harvesting require DALI-2?
No. Standalone controls and other dimming methods can work. Confirm sensor, controller and driver compatibility, grouping and the handover method before selecting a protocol.
Sources and further reading
- DALI Alliance — Sensors and other input devices
- DALI Alliance — Systems and components
- U.S. DOE and GSA — LED Lighting and Controls Guidance for Federal Buildings
- Whole Building Design Guide — Daylighting Photosensor TechNote
Adapted and expanded from the Thai Lumens Lab guide. Reviewed 28 November 2026. Examples are illustrative; check the requirements and measured conditions of each project.